储能对比
CATL TENER vs HyperStrong HyperBlock M (AC version)
两列数据均来自 CATL 和 HyperStrong 的公开发布。生产商未公开的字段标记为「未公开」;我们不进行估算或排名。
CATL
TENER
6.25 MWh
20 英尺集装箱liquid-cooledLFP供货中
HyperStrong
HyperBlock M (AC version)
12.8 MWh
模块化liquid-cooledLFP供货中
规格参数对比
| 字段 | CATL TENER | HyperStrong HyperBlock M (AC version) |
|---|---|---|
| 单机柜最大能量 | 6.25 MWh | 12.8 MWh |
| 单机柜最大功率 | 3.126 MW | 3.2 MW |
| 放电时长 | 2 h | 4 h |
| 分类 | 公用事业级 | 公用事业级 |
| 状态 | 供货中 | 供货中 |
| 电芯化学 | LFP | LFP |
| 电芯容量 | 587 Ah | 601 Ah |
| 电芯配置 | 1P104S×4×8P (pack 1P104S, 4 packs per rack = 1P416S, 8 racks in parallel) | 8P416S / 16P416S |
| 电芯供应商 | 未公开 | 未公开 |
| 形态 | 20 英尺集装箱 | 模块化 |
| 模块类型 | 直流模块 | 交流模块(PCS 集成) |
| PCS 集成 | 否 | 是 |
| 直流电压 | 1331.2 rated; 1040–1500 range V | 1123.2–1497.6 (rated 1331.2) V |
| 散热 | liquid-cooled | liquid-cooled |
| 防护等级 | 未公开 | Container IP55, Pack IP65, PDU IP55 |
| Operating temperature | -30…55 °C | -30…55 °C |
| 尺寸(长 × 宽 × 高) | 未公开 | 6058 × 2438 × 2896 mm |
| 重量 | 45 t | 24 t |
| 能量密度 | 未公开 | 未公开 |
| Round-trip efficiency | 未公开 | 93% |
| 循环寿命 | 8,000 · Cell-level figure from CATL 2026 brochure: 587 Ah cell ≥8,000 cycles (25 °C, 0.5P/0.5P, 70% SOH). System-level cycle life not published; CATL claims zero capacity/power degradation in first five years. | 10,000 · >10000cls@SOH70%, 0.5P, to achieve up to 20 years of operation life guarantee |
| 日历寿命 | 未公开 | 20 y |
| 保修期 | 未公开 | 未公开 |
| 灭火系统 | 未公开 | Combustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protection |
| 代 | TENER (2024); Chinese market designation 天恒 C2-L625 | MagicBlock platform, 2025 |
| 发布 | 2024-04 | 2025-05 |
| Certifications | GB 44240-2024, GB/T 34131-2023, GB/T 36276-2023, GB/T 44026-2024 | EN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120 |
| 公开数据表 | 是 | 是 |
差异对比
仅显示两家生产商均已公开且数值不同的字段。这不是评判——最佳选择取决于项目需求。
- 单机柜最大能量: TENER — 6.25 MWh; HyperBlock M (AC version) — 12.8 MWh
- 单机柜最大功率: TENER — 3.126 MW; HyperBlock M (AC version) — 3.2 MW
- 放电时长: TENER — 2 h; HyperBlock M (AC version) — 4 h
- 电芯容量: TENER — 587 Ah; HyperBlock M (AC version) — 601 Ah
- 电芯配置: TENER — 1P104S×4×8P (pack 1P104S, 4 packs per rack = 1P416S, 8 racks in parallel); HyperBlock M (AC version) — 8P416S / 16P416S
- 形态: TENER — 20 英尺集装箱; HyperBlock M (AC version) — 模块化
- 模块类型: TENER — 直流模块; HyperBlock M (AC version) — 交流模块(PCS 集成)
- PCS 集成: TENER — 否; HyperBlock M (AC version) — 是
- 直流电压: TENER — 1331.2 rated; 1040–1500 range V; HyperBlock M (AC version) — 1123.2–1497.6 (rated 1331.2) V
- 重量: TENER — 45 t; HyperBlock M (AC version) — 24 t
- 循环寿命: TENER — 8,000 · Cell-level figure from CATL 2026 brochure: 587 Ah cell ≥8,000 cycles (25 °C, 0.5P/0.5P, 70% SOH). System-level cycle life not published; CATL claims zero capacity/power degradation in first five years.; HyperBlock M (AC version) — 10,000 · >10000cls@SOH70%, 0.5P, to achieve up to 20 years of operation life guarantee
- 代: TENER — TENER (2024); Chinese market designation 天恒 C2-L625; HyperBlock M (AC version) — MagicBlock platform, 2025
- 发布: TENER — 2024-04; HyperBlock M (AC version) — 2025-05
- Certifications: TENER — GB 44240-2024, GB/T 34131-2023, GB/T 36276-2023, GB/T 44026-2024; HyperBlock M (AC version) — EN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120
仅由其中一家发布:防护等级, 尺寸(长 × 宽 × 高), Round-trip efficiency, 日历寿命, 灭火系统。
变体
CATL TENER 变体
| 规格型号 | 能量 | 功率 | 时长 |
|---|---|---|---|
| 6.25 MWh 0.5P (2 × 1562.82 kW); brochure states 2 h/4 h system compatibility | 6.25 MWh | 3.126 MW | 2 h |
HyperStrong HyperBlock M (AC version) 变体
| 规格型号 | 能量 | 功率 | 时长 |
|---|---|---|---|
| HSL3G71-06400 — 6.4 MWh / 400 kW×4 | 6.4 MWh | 1.6 MW | 4 h |
| HSL3G71-12800 — 12.8 MWh / 400 kW×8 | 12.8 MWh | 3.2 MW | 4 h |
完整产品卡片
查看 CATL TENER →查看 HyperStrong HyperBlock M (AC version) →
其他对比
Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs CATL TENERGotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs HyperStrong HyperBlock M (AC version)Pylontech Container L5000-BAT vs CATL TENERPylontech Container L5000-BAT vs HyperStrong HyperBlock M (AC version)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs CATL TENERSunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs HyperStrong HyperBlock M (AC version)CATL TENER vs Great Power Max-20HC-5000CATL TENER vs HiTHIUM ∞Power 6.25MWh