字段CATL TENERHyperStrong HyperBlock M (AC version)
单机柜最大能量6.25 MWh12.8 MWh
单机柜最大功率3.126 MW3.2 MW
放电时长2 h4 h
分类公用事业级公用事业级
状态供货中供货中
电芯化学LFPLFP
电芯容量587 Ah601 Ah
电芯配置1P104S×4×8P (pack 1P104S, 4 packs per rack = 1P416S, 8 racks in parallel)8P416S / 16P416S
电芯供应商未公开未公开
形态20 英尺集装箱模块化
模块类型直流模块交流模块(PCS 集成)
PCS 集成
直流电压1331.2 rated; 1040–1500 range V1123.2–1497.6 (rated 1331.2) V
散热liquid-cooledliquid-cooled
防护等级未公开Container IP55, Pack IP65, PDU IP55
Operating temperature-30…55 °C-30…55 °C
尺寸(长 × 宽 × 高)未公开6058 × 2438 × 2896 mm
重量45 t24 t
能量密度未公开未公开
Round-trip efficiency未公开93%
循环寿命8,000 · Cell-level figure from CATL 2026 brochure: 587 Ah cell ≥8,000 cycles (25 °C, 0.5P/0.5P, 70% SOH). System-level cycle life not published; CATL claims zero capacity/power degradation in first five years.10,000 · >10000cls@SOH70%, 0.5P, to achieve up to 20 years of operation life guarantee
日历寿命未公开20 y
保修期未公开未公开
灭火系统未公开Combustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protection
TENER (2024); Chinese market designation 天恒 C2-L625MagicBlock platform, 2025
发布2024-042025-05
CertificationsGB 44240-2024, GB/T 34131-2023, GB/T 36276-2023, GB/T 44026-2024EN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120
公开数据表

差异对比

仅显示两家生产商均已公开且数值不同的字段。这不是评判——最佳选择取决于项目需求。

  • 单机柜最大能量: TENER — 6.25 MWh; HyperBlock M (AC version) — 12.8 MWh
  • 单机柜最大功率: TENER — 3.126 MW; HyperBlock M (AC version) — 3.2 MW
  • 放电时长: TENER — 2 h; HyperBlock M (AC version) — 4 h
  • 电芯容量: TENER — 587 Ah; HyperBlock M (AC version) — 601 Ah
  • 电芯配置: TENER — 1P104S×4×8P (pack 1P104S, 4 packs per rack = 1P416S, 8 racks in parallel); HyperBlock M (AC version) — 8P416S / 16P416S
  • 形态: TENER — 20 英尺集装箱; HyperBlock M (AC version) — 模块化
  • 模块类型: TENER — 直流模块; HyperBlock M (AC version) — 交流模块(PCS 集成)
  • PCS 集成: TENER — 否; HyperBlock M (AC version) — 是
  • 直流电压: TENER — 1331.2 rated; 1040–1500 range V; HyperBlock M (AC version) — 1123.2–1497.6 (rated 1331.2) V
  • 重量: TENER — 45 t; HyperBlock M (AC version) — 24 t
  • 循环寿命: TENER — 8,000 · Cell-level figure from CATL 2026 brochure: 587 Ah cell ≥8,000 cycles (25 °C, 0.5P/0.5P, 70% SOH). System-level cycle life not published; CATL claims zero capacity/power degradation in first five years.; HyperBlock M (AC version) — 10,000 · >10000cls@SOH70%, 0.5P, to achieve up to 20 years of operation life guarantee
  • : TENER — TENER (2024); Chinese market designation 天恒 C2-L625; HyperBlock M (AC version) — MagicBlock platform, 2025
  • 发布: TENER — 2024-04; HyperBlock M (AC version) — 2025-05
  • Certifications: TENER — GB 44240-2024, GB/T 34131-2023, GB/T 36276-2023, GB/T 44026-2024; HyperBlock M (AC version) — EN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120

仅由其中一家发布:防护等级, 尺寸(长 × 宽 × 高), Round-trip efficiency, 日历寿命, 灭火系统。

变体

CATL TENER 变体

规格型号能量功率时长
6.25 MWh 0.5P (2 × 1562.82 kW); brochure states 2 h/4 h system compatibility6.25 MWh3.126 MW2 h

HyperStrong HyperBlock M (AC version) 变体

规格型号能量功率时长
HSL3G71-06400 — 6.4 MWh / 400 kW×46.4 MWh1.6 MW4 h
HSL3G71-12800 — 12.8 MWh / 400 kW×812.8 MWh3.2 MW4 h

完整产品卡片

查看 CATL TENER →查看 HyperStrong HyperBlock M (AC version) →

其他对比

Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs CATL TENERGotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs HyperStrong HyperBlock M (AC version)Pylontech Container L5000-BAT vs CATL TENERPylontech Container L5000-BAT vs HyperStrong HyperBlock M (AC version)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs CATL TENERSunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs HyperStrong HyperBlock M (AC version)CATL TENER vs Great Power Max-20HC-5000CATL TENER vs HiTHIUM ∞Power 6.25MWh