▮▮Coloprice

储能对比

Great Power Max-20HC-5000 vs HyperStrong HyperBlock M (AC version)

两列数据均来自 Great Power 和 HyperStrong 的公开发布。生产商未公开的字段标记为「未公开」;我们不进行估算或排名。

规格参数对比

字段Great Power Max-20HC-5000HyperStrong HyperBlock M (AC version)
单机柜最大能量5 MWh12.8 MWh
单机柜最大功率2.5 MW3.2 MW
放电时长2 h4 h
分类公用事业级公用事业级
状态供货中供货中
电芯化学LFPLFP
电芯容量314 Ah601 Ah
电芯配置1P416S ×128P416S / 16P416S
电芯供应商未公开未公开
形态20 英尺集装箱模块化
模块类型直流模块交流模块(PCS 集成)
PCS 集成
直流电压1164.8–1497.8 V1123.2–1497.6 (rated 1331.2) V
散热liquid-cooledliquid-cooled
防护等级IP55Container IP55, Pack IP65, PDU IP55
Operating temperature-35…60 (discharge), -30…50 (charge) °C-30…55 °C
尺寸(长 × 宽 × 高)6058 × 2438 × 2896 mm6058 × 2438 × 2896 mm
重量46 t24 t
能量密度未公开未公开
Round-trip efficiency95%93%
循环寿命未公开10,000 · >10000cls@SOH70%, 0.5P, to achieve up to 20 years of operation life guarantee
日历寿命未公开20 y
保修期未公开未公开
灭火系统aerosol + waterCombustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protection
2024MagicBlock platform, 2025
发布2024-092025-05
CertificationsGB/T 36276, IEC 61000, IEC 62619, IEC 62933, NFPA 68, NFPA 69, NFPA 72, NFPA 855, UL 1973, UL 9540, UL 9540AEN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120
公开数据表

差异对比

仅显示两家生产商均已公开且数值不同的字段。这不是评判——最佳选择取决于项目需求。

  • 单机柜最大能量: Max-20HC-5000 — 5 MWh; HyperBlock M (AC version) — 12.8 MWh
  • 单机柜最大功率: Max-20HC-5000 — 2.5 MW; HyperBlock M (AC version) — 3.2 MW
  • 放电时长: Max-20HC-5000 — 2 h; HyperBlock M (AC version) — 4 h
  • 电芯容量: Max-20HC-5000 — 314 Ah; HyperBlock M (AC version) — 601 Ah
  • 电芯配置: Max-20HC-5000 — 1P416S ×12; HyperBlock M (AC version) — 8P416S / 16P416S
  • 形态: Max-20HC-5000 — 20 英尺集装箱; HyperBlock M (AC version) — 模块化
  • 模块类型: Max-20HC-5000 — 直流模块; HyperBlock M (AC version) — 交流模块(PCS 集成)
  • PCS 集成: Max-20HC-5000 — 否; HyperBlock M (AC version) — 是
  • 直流电压: Max-20HC-5000 — 1164.8–1497.8 V; HyperBlock M (AC version) — 1123.2–1497.6 (rated 1331.2) V
  • 防护等级: Max-20HC-5000 — IP55; HyperBlock M (AC version) — Container IP55, Pack IP65, PDU IP55
  • Operating temperature: Max-20HC-5000 — -35…60 (discharge), -30…50 (charge) °C; HyperBlock M (AC version) — -30…55 °C
  • 重量: Max-20HC-5000 — 46 t; HyperBlock M (AC version) — 24 t
  • Round-trip efficiency: Max-20HC-5000 — 95%; HyperBlock M (AC version) — 93%
  • 灭火系统: Max-20HC-5000 — aerosol + water; HyperBlock M (AC version) — Combustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protection
  • : Max-20HC-5000 — 2024; HyperBlock M (AC version) — MagicBlock platform, 2025
  • 发布: Max-20HC-5000 — 2024-09; HyperBlock M (AC version) — 2025-05
  • Certifications: Max-20HC-5000 — GB/T 36276, IEC 61000, IEC 62619, IEC 62933, NFPA 68, NFPA 69, NFPA 72, NFPA 855, UL 1973, UL 9540, UL 9540A; HyperBlock M (AC version) — EN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120

仅由其中一家发布:循环寿命, 日历寿命。

变体

Great Power Max-20HC-5000 变体

规格型号能量功率时长
5.0 MWh @0.5C (≤417 kW ×6 / 1.25 MW ×2)5 MWh2.5 MW2 h

HyperStrong HyperBlock M (AC version) 变体

规格型号能量功率时长
HSL3G71-06400 — 6.4 MWh / 400 kW×46.4 MWh1.6 MW4 h
HSL3G71-12800 — 12.8 MWh / 400 kW×812.8 MWh3.2 MW4 h

完整产品卡片

查看 Great Power Max-20HC-5000 →查看 HyperStrong HyperBlock M (AC version) →

其他对比

Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs Great Power Max-20HC-5000Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs HyperStrong HyperBlock M (AC version)Pylontech Container L5000-BAT vs Great Power Max-20HC-5000Pylontech Container L5000-BAT vs HyperStrong HyperBlock M (AC version)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs Great Power Max-20HC-5000Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs HyperStrong HyperBlock M (AC version)CATL TENER vs Great Power Max-20HC-5000CATL TENER vs HyperStrong HyperBlock M (AC version)