FieldGreat Power Max-20HC-5000HyperStrong HyperBlock M (AC version)
Max energy per enclosure5 MWh12.8 MWh
Max power per enclosure2.5 MW3.2 MW
Published durations2 h4 h
Segmentutility-scaleutility-scale
Statusshippingshipping
Cell chemistryLFPLFP
Cell capacity314 Ah601 Ah
Cell configuration1P416S ×128P416S / 16P416S
Cell suppliernot publishednot published
Form factor20 ft containermodular block
Block typeDC blockAC block (PCS integrated)
PCS integratednoyes
DC voltage1164.8–1497.8 V1123.2–1497.6 (rated 1331.2) V
Coolingliquid-cooledliquid-cooled
Ingress protectionIP55Container IP55, Pack IP65, PDU IP55
Operating temperature-35…60 (discharge), -30…50 (charge) °C-30…55 °C
Dimensions (L × W × H)6058 × 2438 × 2896 mm6058 × 2438 × 2896 mm
Weight46 t24 t
Energy densitynot publishednot published
Round-trip efficiency95%93%
Cycle lifenot published10,000 · >10000cls@SOH70%, 0.5P, to achieve up to 20 years of operation life guarantee
Calendar lifenot published20 y
Warrantynot publishednot published
Fire suppressionaerosol + waterCombustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protection
Generation2024MagicBlock platform, 2025
Announced2024-092025-05
CertificationsGB/T 36276, IEC 61000, IEC 62619, IEC 62933, NFPA 68, NFPA 69, NFPA 72, NFPA 855, UL 1973, UL 9540, UL 9540AEN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120
Public datasheetyesyes

Where they differ

Only fields both manufacturers publish and where the values are not identical. Not a judgement — the right choice depends on the project.

  • Max energy per enclosure: Max-20HC-5000 — 5 MWh; HyperBlock M (AC version) — 12.8 MWh
  • Max power per enclosure: Max-20HC-5000 — 2.5 MW; HyperBlock M (AC version) — 3.2 MW
  • Published durations: Max-20HC-5000 — 2 h; HyperBlock M (AC version) — 4 h
  • Cell capacity: Max-20HC-5000 — 314 Ah; HyperBlock M (AC version) — 601 Ah
  • Cell configuration: Max-20HC-5000 — 1P416S ×12; HyperBlock M (AC version) — 8P416S / 16P416S
  • Form factor: Max-20HC-5000 — 20 ft container; HyperBlock M (AC version) — modular block
  • Block type: Max-20HC-5000 — DC block; HyperBlock M (AC version) — AC block (PCS integrated)
  • PCS integrated: Max-20HC-5000 — no; HyperBlock M (AC version) — yes
  • DC voltage: Max-20HC-5000 — 1164.8–1497.8 V; HyperBlock M (AC version) — 1123.2–1497.6 (rated 1331.2) V
  • Ingress protection: Max-20HC-5000 — IP55; HyperBlock M (AC version) — Container IP55, Pack IP65, PDU IP55
  • Operating temperature: Max-20HC-5000 — -35…60 (discharge), -30…50 (charge) °C; HyperBlock M (AC version) — -30…55 °C
  • Weight: Max-20HC-5000 — 46 t; HyperBlock M (AC version) — 24 t
  • Round-trip efficiency: Max-20HC-5000 — 95%; HyperBlock M (AC version) — 93%
  • Fire suppression: Max-20HC-5000 — aerosol + water; HyperBlock M (AC version) — Combustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protection
  • Generation: Max-20HC-5000 — 2024; HyperBlock M (AC version) — MagicBlock platform, 2025
  • Announced: Max-20HC-5000 — 2024-09; HyperBlock M (AC version) — 2025-05
  • Certifications: Max-20HC-5000 — GB/T 36276, IEC 61000, IEC 62619, IEC 62933, NFPA 68, NFPA 69, NFPA 72, NFPA 855, UL 1973, UL 9540, UL 9540A; HyperBlock M (AC version) — EN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120

Published by only one of the two: Cycle life, Calendar life.

Variants

Great Power Max-20HC-5000 variants

VariantsEnergyPowerDuration
5.0 MWh @0.5C (≤417 kW ×6 / 1.25 MW ×2)5 MWh2.5 MW2 h

HyperStrong HyperBlock M (AC version) variants

VariantsEnergyPowerDuration
HSL3G71-06400 — 6.4 MWh / 400 kW×46.4 MWh1.6 MW4 h
HSL3G71-12800 — 12.8 MWh / 400 kW×812.8 MWh3.2 MW4 h

Full model cards

Open Great Power Max-20HC-5000 →Open HyperStrong HyperBlock M (AC version) →

Other comparisons

Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs Great Power Max-20HC-5000Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs HyperStrong HyperBlock M (AC version)Pylontech Container L5000-BAT vs Great Power Max-20HC-5000Pylontech Container L5000-BAT vs HyperStrong HyperBlock M (AC version)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs Great Power Max-20HC-5000Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs HyperStrong HyperBlock M (AC version)CATL TENER vs Great Power Max-20HC-5000CATL TENER vs HyperStrong HyperBlock M (AC version)