Perbandingan BESS
CRRC Zhuzhou Institute 6.X Liquid Cooling Energy Storage System vs HyperStrong HyperBlock M (AC version)
Kedua kolom berasal dari informasi yang CRRC Zhuzhou Institute dan HyperStrong publikasikan. Bidang yang tidak dipublikasikan oleh salah satu produsen ditandai «tidak dipublikasikan»; kami tidak melakukan estimasi atau peringkat.
CRRC Zhuzhou Institute
6.X Liquid Cooling Energy Storage System
6,901 MWh
kontainer 20 ftberpendingin cairanLFPpengiriman
HyperStrong
HyperBlock M (AC version)
12,8 MWh
blok modularberpendingin cairanLFPpengiriman
Spesifikasi berdampingan
| Bidang | CRRC Zhuzhou Institute 6.X Liquid Cooling Energy Storage System | HyperStrong HyperBlock M (AC version) |
|---|---|---|
| Energi maks per enklosur | 6,901 MWh | 12,8 MWh |
| Daya maks per enklosur | tidak dipublikasikan | 3,2 MW |
| Durasi yang dipublikasikan | 2 h · 4 h | 4 h |
| Segmen | skala utilitas | skala utilitas |
| Status | pengiriman | pengiriman |
| Kimia sel | LFP | LFP |
| Kapasitas sel | 587 Ah | 601 Ah |
| Konfigurasi sel | 416S4P (10-ft) / 416S8P (20-ft) | 8P416S / 16P416S |
| Pemasok sel | tidak dipublikasikan | tidak dipublikasikan |
| Faktor bentuk | kontainer 20 ft | blok modular |
| Jenis blok | blok DC | blok AC (PCS terintegrasi) |
| PCS terintegrasi | tidak | ya |
| Tegangan DC | 1081.6–1497.6 V | 1123.2–1497.6 (rated 1331.2) V |
| Pendinginan | berpendingin cairan | berpendingin cairan |
| Perlindungan IP | IP55 | Container IP55, Pack IP65, PDU IP55 |
| Suhu operasi | -30…55 °C | -30…55 °C |
| Dimensi (P × L × T) | 6058 × 2438 × 2896 mm | 6058 × 2438 × 2896 mm |
| Berat | 48 t | 24 t |
| Kepadatan energi | tidak dipublikasikan | tidak dipublikasikan |
| Efisiensi bolak-balik | tidak dipublikasikan | 93% |
| Masa pakai siklus | tidak dipublikasikan | 10.000 · >10000cls@SOH70%, 0.5P, to achieve up to 20 years of operation life guarantee |
| Masa pakai kalender | tidak dipublikasikan | 20 y |
| Garansi | tidak dipublikasikan | tidak dipublikasikan |
| Supresi api | Aerosol-based suppression system; flooded fire protection systems (options); fire alarm panel, heat and smoke detection, alarm bell and strobe | Combustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protection |
| Generasi | 6.X (2026) | MagicBlock platform, 2025 |
| Diumumkan | 2026-01 | 2025-05 |
| Sertifikasi | IEC 61000, IEC 62477-1, IEC 62619, IEC 62933-5-2, IEC 63056, UL9540A, UN3536, UN38.3 | EN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120 |
| Lembar data publik | ya | ya |
Perbedaan
Hanya bidang yang dipublikasikan oleh kedua produsen dan di mana nilainya tidak identik. Bukan penilaian — pilihan yang tepat bergantung pada proyek.
- Energi maks per enklosur: 6.X Liquid Cooling Energy Storage System — 6,901 MWh; HyperBlock M (AC version) — 12,8 MWh
- Durasi yang dipublikasikan: 6.X Liquid Cooling Energy Storage System — 2 h · 4 h; HyperBlock M (AC version) — 4 h
- Kapasitas sel: 6.X Liquid Cooling Energy Storage System — 587 Ah; HyperBlock M (AC version) — 601 Ah
- Konfigurasi sel: 6.X Liquid Cooling Energy Storage System — 416S4P (10-ft) / 416S8P (20-ft); HyperBlock M (AC version) — 8P416S / 16P416S
- Faktor bentuk: 6.X Liquid Cooling Energy Storage System — kontainer 20 ft; HyperBlock M (AC version) — blok modular
- Jenis blok: 6.X Liquid Cooling Energy Storage System — blok DC; HyperBlock M (AC version) — blok AC (PCS terintegrasi)
- PCS terintegrasi: 6.X Liquid Cooling Energy Storage System — tidak; HyperBlock M (AC version) — ya
- Tegangan DC: 6.X Liquid Cooling Energy Storage System — 1081.6–1497.6 V; HyperBlock M (AC version) — 1123.2–1497.6 (rated 1331.2) V
- Perlindungan IP: 6.X Liquid Cooling Energy Storage System — IP55; HyperBlock M (AC version) — Container IP55, Pack IP65, PDU IP55
- Berat: 6.X Liquid Cooling Energy Storage System — 48 t; HyperBlock M (AC version) — 24 t
- Supresi api: 6.X Liquid Cooling Energy Storage System — Aerosol-based suppression system; flooded fire protection systems (options); fire alarm panel, heat and smoke detection, alarm bell and strobe; HyperBlock M (AC version) — Combustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protection
- Generasi: 6.X Liquid Cooling Energy Storage System — 6.X (2026); HyperBlock M (AC version) — MagicBlock platform, 2025
- Diumumkan: 6.X Liquid Cooling Energy Storage System — 2026-01; HyperBlock M (AC version) — 2025-05
- Sertifikasi: 6.X Liquid Cooling Energy Storage System — IEC 61000, IEC 62477-1, IEC 62619, IEC 62933-5-2, IEC 63056, UL9540A, UN3536, UN38.3; HyperBlock M (AC version) — EN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120
Hanya dipublikasikan oleh salah satu dari keduanya: Daya maks per enklosur, Efisiensi bolak-balik, Masa pakai siklus, Masa pakai kalender.
Varian
Varian CRRC Zhuzhou Institute 6.X Liquid Cooling Energy Storage System
| Varian | Energi | Daya | Durasi |
|---|---|---|---|
| CESS-L3125-EU-0.5C — 3.125 MWh (10-ft, 587 Ah) | 3,125 MWh | tidak dipublikasikan | 2 h |
| CESS-L3125-EU-0.25C — 3.125 MWh (10-ft, 587 Ah) | 3,125 MWh | tidak dipublikasikan | 4 h |
| CESS-L3450-EU-0.5C — 3.450 MWh (10-ft, 648 Ah) | 3,45 MWh | tidak dipublikasikan | 2 h |
| CESS-L6250-EU-0.5C — 6.250 MWh (20-ft, 587 Ah) | 6,25 MWh | tidak dipublikasikan | 2 h |
| CESS-L6250-EU-0.25C — 6.250 MWh (20-ft, 587 Ah) | 6,25 MWh | tidak dipublikasikan | 4 h |
| CESS-L6901-EU-0.5C — 6.901 MWh (20-ft, 648 Ah) | 6,901 MWh | tidak dipublikasikan | 2 h |
Varian HyperStrong HyperBlock M (AC version)
| Varian | Energi | Daya | Durasi |
|---|---|---|---|
| HSL3G71-06400 — 6.4 MWh / 400 kW×4 | 6,4 MWh | 1,6 MW | 4 h |
| HSL3G71-12800 — 12.8 MWh / 400 kW×8 | 12,8 MWh | 3,2 MW | 4 h |
Kartu model lengkap
Buka CRRC Zhuzhou Institute 6.X Liquid Cooling Energy Storage System →Buka HyperStrong HyperBlock M (AC version) →
Perbandingan lainnya
Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs CRRC Zhuzhou Institute 6.X Liquid Cooling Energy Storage SystemGotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs HyperStrong HyperBlock M (AC version)Pylontech Container L5000-BAT vs CRRC Zhuzhou Institute 6.X Liquid Cooling Energy Storage SystemPylontech Container L5000-BAT vs HyperStrong HyperBlock M (AC version)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs CRRC Zhuzhou Institute 6.X Liquid Cooling Energy Storage SystemSunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs HyperStrong HyperBlock M (AC version)CATL TENER vs CRRC Zhuzhou Institute 6.X Liquid Cooling Energy Storage SystemCATL TENER vs HyperStrong HyperBlock M (AC version)