▮▮Coloprice

Wärtsilä Energy Storage · utility-scale

Wärtsilä Energy Storage GridSolve Quantum2

shipping

20 ft containerDC blockhybrid coolingBNEF Tier 1

Everything below comes from what Wärtsilä Energy Storage publishes about the GridSolve Quantum2: the datasheet, the product page and press releases. Where a figure is not published, the field says so — we do not estimate.

Schematic illustration — not a manufacturer photo

Variants

4.073 MWh

Verified 2026-08

Variants

Energy figures are nominal (beginning of life) as published by the manufacturer. One model, several duration options — the same enclosure with different power ratings.

VariantsEnergyPowerDuration
4073 kWh DC block (0.1–0.5 C)4.073 MWhnot publishednot published

Specifications

Cell chemistrynot published
Cell capacitynot published
Cell configuration10P x 8S x 52S
Cell suppliernot published
Form factor20 ft container
Block typeDC block
PCS integratedno
DC voltage1164–1498 V
Coolinghybrid cooling
Ingress protectionnot published
Operating temperature-30…50 °C
Dimensions (L × W × H)6100 × 2400 × 2800 mm
Weight38 t
Energy densitynot published
Round-trip efficiencynot published
Cycle lifenot published
Calendar lifenot published
Warrantynot published
Fire suppressionnot published
Generation2024
Announced2024-03

Certifications

UL 9540A – Unit-level and container-level fire testingNFPA 855 (2023 & 2026 editions)Large-Scale Fire Test – Third-party validatedActive Ignition Mitigation System (AIMS) TestingIEC 62443-4Noise Compliance Testing

Key facts

  • 4,073 kWh nominal pre-installed DC block in a 20 ft high-cube ISO container; configuration 10P x 8S x 52S
  • Nominal 1331 VDC (1164–1498 VDC), 0.1–0.5 C; auxiliary peak load 30 kW at 480 V 60 Hz or 380–415 V 50/60 Hz
  • Weight 38,000 kg; 6.1 × 2.4 × 2.8 m; configurable hybrid cooling with water/glycol coolant; -30…+50 °C
  • Liquid-cooled IP67 modules; press release states modules can be sourced from various manufacturers (cell supplier not named)
  • Gas detection ports and H₂ sensors; noise-optimised fan system; manufactured by RCT Power (Malaysia)

What Wärtsilä Energy Storage does not publish for this model

These fields are empty because no public datasheet or release states them. That is information too: ask for these numbers before you shortlist.

Cell chemistryCell capacityCell supplierIngress protectionEnergy densityRound-trip efficiencyCycle lifeCalendar lifeWarrantyFire suppression

Similar systems from other manufacturers

Sourcing quote for Wärtsilä Energy Storage GridSolve Quantum2

Coloprice is published by Dream View, a China-sourcing company. For commercial-scale projects we buy BESS containers factory-direct — verified manufacturer, certification review, pre-shipment inspection, export and freight — for a flat 10% fee.

We reply within one business day. No spam, no reselling your contacts.

Sources: Quantum2 solution sheet (PDF) · Wärtsilä introduces Quantum2 (press release 2024-03-18) · GridSolve BESS portfolio page