▮▮Coloprice

BESS comparison

CLOU Electronics Aqua-C3.0 (S/H Version) vs LG Energy Solution JF2 AC LINK (2HR / 4HR)

Both columns come from what CLOU Electronics and LG Energy Solution publish. Fields either maker does not publish are marked «not published»; we do not estimate or rank.

Specifications side by side

FieldCLOU Electronics Aqua-C3.0 (S/H Version)LG Energy Solution JF2 AC LINK (2HR / 4HR)
Max energy per enclosure6.251 MWh5.11 MWh
Max power per enclosure3.125 MW2.55 MW
Published durations2 h · 4 h2 h · 4 h
Segmentutility-scaleutility-scale
Statusshippingshipping
Cell chemistryLFPLFP
Cell capacity587 Ahnot published
Cell configuration1P416S×8 (8P416S)14 packs in series × 6 racks in parallel (2HR)
Cell suppliernot publishednot published
Form factor20 ft containermodular block
Block typeAC block (PCS integrated)AC block (PCS integrated)
PCS integratedyesyes
DC voltage1123.2–1497.6 Vnot published
Coolingliquid-cooledliquid-cooled
Ingress protectionIP55IP55
Operating temperature-30…50 (55 optional on H) °C-30…50 °C
Dimensions (L × W × H)6058 × 2438 × 2896 mm7020 × 2570 × 2900 mm
Weight47 t48 t
Energy densitynot publishednot published
Round-trip efficiencynot publishednot published
Cycle lifenot publishednot published
Calendar lifenot publishednot published
Warrantynot publishednot published
Fire suppressionsmoke/heat detectors, FACP, ventilation (NFPA 69), dry pipes with sprinklers, aerosol (optional on S), deflagration vent panel (optional)gas detection and active venting system, fire detection and alarm system
Generation3.02024
Announced2025-062024-11
CertificationsCE, CEI 0-16, EN 50549, EN 62477-1, G99, IEC 61000, IEC 62477-1, IEC 62619, IEC 62933, IEC 62993-5-2, IEC 63056, NTS 2.1, NTS SENP 1.1, UL 9540A, UN 38.3/UN 3536, VDE-AR-N 4110, VDE-AR-N 4120IEEE1547, IFC/CFC, NFPA 69, NFPA 72, NFPA 855, UL1642, UL1741 (SA, SB), UL1973, UL9540, UL9540A and large-scale fire testing, UN 38.3
Public datasheetyesyes

Where they differ

Only fields both manufacturers publish and where the values are not identical. Not a judgement — the right choice depends on the project.

  • Max energy per enclosure: Aqua-C3.0 (S/H Version) — 6.251 MWh; JF2 AC LINK (2HR / 4HR) — 5.11 MWh
  • Max power per enclosure: Aqua-C3.0 (S/H Version) — 3.125 MW; JF2 AC LINK (2HR / 4HR) — 2.55 MW
  • Cell configuration: Aqua-C3.0 (S/H Version) — 1P416S×8 (8P416S); JF2 AC LINK (2HR / 4HR) — 14 packs in series × 6 racks in parallel (2HR)
  • Form factor: Aqua-C3.0 (S/H Version) — 20 ft container; JF2 AC LINK (2HR / 4HR) — modular block
  • Operating temperature: Aqua-C3.0 (S/H Version) — -30…50 (55 optional on H) °C; JF2 AC LINK (2HR / 4HR) — -30…50 °C
  • Dimensions (L × W × H): Aqua-C3.0 (S/H Version) — 6058 × 2438 × 2896 mm; JF2 AC LINK (2HR / 4HR) — 7020 × 2570 × 2900 mm
  • Weight: Aqua-C3.0 (S/H Version) — 47 t; JF2 AC LINK (2HR / 4HR) — 48 t
  • Fire suppression: Aqua-C3.0 (S/H Version) — smoke/heat detectors, FACP, ventilation (NFPA 69), dry pipes with sprinklers, aerosol (optional on S), deflagration vent panel (optional); JF2 AC LINK (2HR / 4HR) — gas detection and active venting system, fire detection and alarm system
  • Generation: Aqua-C3.0 (S/H Version) — 3.0; JF2 AC LINK (2HR / 4HR) — 2024
  • Announced: Aqua-C3.0 (S/H Version) — 2025-06; JF2 AC LINK (2HR / 4HR) — 2024-11
  • Certifications: Aqua-C3.0 (S/H Version) — CE, CEI 0-16, EN 50549, EN 62477-1, G99, IEC 61000, IEC 62477-1, IEC 62619, IEC 62933, IEC 62993-5-2, IEC 63056, NTS 2.1, NTS SENP 1.1, UL 9540A, UN 38.3/UN 3536, VDE-AR-N 4110, VDE-AR-N 4120; JF2 AC LINK (2HR / 4HR) — IEEE1547, IFC/CFC, NFPA 69, NFPA 72, NFPA 855, UL1642, UL1741 (SA, SB), UL1973, UL9540, UL9540A and large-scale fire testing, UN 38.3

Published by only one of the two: Cell capacity, DC voltage.

Variants

CLOU Electronics Aqua-C3.0 (S/H Version) variants

VariantsEnergyPowerDuration
Aqua-C3.0H 6250 kWh / 3125 kW @0.5CP (DC, HV box)6.25 MWh3.125 MW2 h
Aqua-C3.0S 6251 kWh / 1563 kVA (string PCS)6.251 MWh1.563 MW4 h

LG Energy Solution JF2 AC LINK (2HR / 4HR) variants

VariantsEnergyPowerDuration
JF2 2HR AC LINK — 5.11 MWh / 2.55 MW, 690 Vrms, 0.5 CP5.11 MWh2.55 MW2 h
JF2 4HR AC LINK — 5.11 MWh / 1.32 MW (6 × 220 kVA), 690 Vrms, 0.25 CP5.11 MWh1.32 MW4 h

Full model cards

Open CLOU Electronics Aqua-C3.0 (S/H Version) →Open LG Energy Solution JF2 AC LINK (2HR / 4HR) →

Other comparisons

Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs LG Energy Solution JF2 AC LINK (2HR / 4HR)Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs CLOU Electronics Aqua-C3.0 (S/H Version)Pylontech Container L5000-BAT vs LG Energy Solution JF2 AC LINK (2HR / 4HR)Pylontech Container L5000-BAT vs CLOU Electronics Aqua-C3.0 (S/H Version)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs LG Energy Solution JF2 AC LINK (2HR / 4HR)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs CLOU Electronics Aqua-C3.0 (S/H Version)CATL TENER vs LG Energy Solution JF2 AC LINK (2HR / 4HR)CATL TENER vs CLOU Electronics Aqua-C3.0 (S/H Version)