▮▮Coloprice

BESS comparison

CLOU Electronics Aqua-C3.0 (S/H Version) vs Great Power Max-20HC-5000

Both columns come from what CLOU Electronics and Great Power publish. Fields either maker does not publish are marked «not published»; we do not estimate or rank.

Specifications side by side

FieldCLOU Electronics Aqua-C3.0 (S/H Version)Great Power Max-20HC-5000
Max energy per enclosure6.251 MWh5 MWh
Max power per enclosure3.125 MW2.5 MW
Published durations2 h · 4 h2 h
Segmentutility-scaleutility-scale
Statusshippingshipping
Cell chemistryLFPLFP
Cell capacity587 Ah314 Ah
Cell configuration1P416S×8 (8P416S)1P416S ×12
Cell suppliernot publishednot published
Form factor20 ft container20 ft container
Block typeAC block (PCS integrated)DC block
PCS integratedyesno
DC voltage1123.2–1497.6 V1164.8–1497.8 V
Coolingliquid-cooledliquid-cooled
Ingress protectionIP55IP55
Operating temperature-30…50 (55 optional on H) °C-35…60 (discharge), -30…50 (charge) °C
Dimensions (L × W × H)6058 × 2438 × 2896 mm6058 × 2438 × 2896 mm
Weight47 t46 t
Energy densitynot publishednot published
Round-trip efficiencynot published95%
Cycle lifenot publishednot published
Calendar lifenot publishednot published
Warrantynot publishednot published
Fire suppressionsmoke/heat detectors, FACP, ventilation (NFPA 69), dry pipes with sprinklers, aerosol (optional on S), deflagration vent panel (optional)aerosol + water
Generation3.02024
Announced2025-062024-09
CertificationsCE, CEI 0-16, EN 50549, EN 62477-1, G99, IEC 61000, IEC 62477-1, IEC 62619, IEC 62933, IEC 62993-5-2, IEC 63056, NTS 2.1, NTS SENP 1.1, UL 9540A, UN 38.3/UN 3536, VDE-AR-N 4110, VDE-AR-N 4120GB/T 36276, IEC 61000, IEC 62619, IEC 62933, NFPA 68, NFPA 69, NFPA 72, NFPA 855, UL 1973, UL 9540, UL 9540A
Public datasheetyesyes

Where they differ

Only fields both manufacturers publish and where the values are not identical. Not a judgement — the right choice depends on the project.

  • Max energy per enclosure: Aqua-C3.0 (S/H Version) — 6.251 MWh; Max-20HC-5000 — 5 MWh
  • Max power per enclosure: Aqua-C3.0 (S/H Version) — 3.125 MW; Max-20HC-5000 — 2.5 MW
  • Published durations: Aqua-C3.0 (S/H Version) — 2 h · 4 h; Max-20HC-5000 — 2 h
  • Cell capacity: Aqua-C3.0 (S/H Version) — 587 Ah; Max-20HC-5000 — 314 Ah
  • Cell configuration: Aqua-C3.0 (S/H Version) — 1P416S×8 (8P416S); Max-20HC-5000 — 1P416S ×12
  • Block type: Aqua-C3.0 (S/H Version) — AC block (PCS integrated); Max-20HC-5000 — DC block
  • PCS integrated: Aqua-C3.0 (S/H Version) — yes; Max-20HC-5000 — no
  • DC voltage: Aqua-C3.0 (S/H Version) — 1123.2–1497.6 V; Max-20HC-5000 — 1164.8–1497.8 V
  • Operating temperature: Aqua-C3.0 (S/H Version) — -30…50 (55 optional on H) °C; Max-20HC-5000 — -35…60 (discharge), -30…50 (charge) °C
  • Weight: Aqua-C3.0 (S/H Version) — 47 t; Max-20HC-5000 — 46 t
  • Fire suppression: Aqua-C3.0 (S/H Version) — smoke/heat detectors, FACP, ventilation (NFPA 69), dry pipes with sprinklers, aerosol (optional on S), deflagration vent panel (optional); Max-20HC-5000 — aerosol + water
  • Generation: Aqua-C3.0 (S/H Version) — 3.0; Max-20HC-5000 — 2024
  • Announced: Aqua-C3.0 (S/H Version) — 2025-06; Max-20HC-5000 — 2024-09
  • Certifications: Aqua-C3.0 (S/H Version) — CE, CEI 0-16, EN 50549, EN 62477-1, G99, IEC 61000, IEC 62477-1, IEC 62619, IEC 62933, IEC 62993-5-2, IEC 63056, NTS 2.1, NTS SENP 1.1, UL 9540A, UN 38.3/UN 3536, VDE-AR-N 4110, VDE-AR-N 4120; Max-20HC-5000 — GB/T 36276, IEC 61000, IEC 62619, IEC 62933, NFPA 68, NFPA 69, NFPA 72, NFPA 855, UL 1973, UL 9540, UL 9540A

Published by only one of the two: Round-trip efficiency.

Variants

CLOU Electronics Aqua-C3.0 (S/H Version) variants

VariantsEnergyPowerDuration
Aqua-C3.0H 6250 kWh / 3125 kW @0.5CP (DC, HV box)6.25 MWh3.125 MW2 h
Aqua-C3.0S 6251 kWh / 1563 kVA (string PCS)6.251 MWh1.563 MW4 h

Great Power Max-20HC-5000 variants

VariantsEnergyPowerDuration
5.0 MWh @0.5C (≤417 kW ×6 / 1.25 MW ×2)5 MWh2.5 MW2 h

Full model cards

Open CLOU Electronics Aqua-C3.0 (S/H Version) →Open Great Power Max-20HC-5000 →

Other comparisons

Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs Great Power Max-20HC-5000Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs CLOU Electronics Aqua-C3.0 (S/H Version)Pylontech Container L5000-BAT vs Great Power Max-20HC-5000Pylontech Container L5000-BAT vs CLOU Electronics Aqua-C3.0 (S/H Version)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs Great Power Max-20HC-5000Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs CLOU Electronics Aqua-C3.0 (S/H Version)CATL TENER vs Great Power Max-20HC-5000CATL TENER vs CLOU Electronics Aqua-C3.0 (S/H Version)