Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs Trina Storage Elementa 2

Both columns come from what Sunwoda Energy and Trina Storage publish. Fields either maker does not publish are marked «not published»; we do not estimate or rank.

Specifications side by side

FieldSunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2)Trina Storage Elementa 2
Max energy per enclosure5.015 MWh5.015 MWh
Max power per enclosure2.508 MWnot published
Published durations2 hnot published
Segmentutility-scaleutility-scale
Statusshippingshipping
Cell chemistryLFPLFP
Cell capacity314 Ah314 Ah
Cell configuration4170 kWh: 1P104S packs (104.49 kWh), 1P416S racks (417 kWh) x10; 5015 kWh: 12P416S1P416S12P
Cell suppliernot publishednot published
Form factor20 ft container20 ft container
Block typeDC blockDC block
PCS integratednono
DC voltage4170: 1164.8–1497.6 (rated 1331.2); 5015: 1040–1500 (nominal 1331.2) V1123.2–1497.6 V
Coolingliquid-cooledliquid-cooled
Ingress protectionIP55 / NEMA 3RIP55 (container, excl. TMS); IP67 module
Operating temperature4170: -30…60; 5015: -30…55 °C-30…50 °C
Dimensions (L × W × H)6058 × 2438 × 2896 mm6058 × 2438 × 2896 mm
Weight41 t42.5 t
Energy densitynot publishednot published
Round-trip efficiency93%not published
Cycle life10,000 · Brochure (2023-11) for 314 Ah cell / NoahX-1500/4170: '10000 cycles @25℃, 0.5CP/0.5CP'. Press release (2023-09) claims cell cycle life 'exceeding 12,000 cycles' and product page for the 314 Ah cell lists 12000 cycles10,000 · Datasheet claim: 'up to 10,000 cycles with 0 degradation in first half year'; test conditions not published
Calendar life20 ynot published
Warrantynot publishednot published
Fire suppressionWater FSS / aerosol (optional); pack-level fire suppression, combustible gas emission and explosion venting (press release)automatic aerosol-based fire suppression system; water-based suppression optional; heat/smoke/gas sensors, active ventilation
GenerationNoahX 2.0, 20232
Announced2023-09not published
CertificationsAS3000, GB36276, IEC61000, IEC62477, IEC62619, IEC62933, NFPA68/69, NFPA855, UL1973, UL9540A, UN3536, UN38.3CE, IEC 61000-6-2/4, IEC 62477-1, IEC 62619, IEC 62933-5-2, IEC 63056, UL 1973, UL 9540, UL 9540A, UN38.3
Public datasheetyesyes

Where they differ

Only fields both manufacturers publish and where the values are not identical. Not a judgement — the right choice depends on the project.

  • Cell configuration: NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) — 4170 kWh: 1P104S packs (104.49 kWh), 1P416S racks (417 kWh) x10; 5015 kWh: 12P416S; Elementa 2 — 1P416S12P
  • DC voltage: NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) — 4170: 1164.8–1497.6 (rated 1331.2); 5015: 1040–1500 (nominal 1331.2) V; Elementa 2 — 1123.2–1497.6 V
  • Ingress protection: NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) — IP55 / NEMA 3R; Elementa 2 — IP55 (container, excl. TMS); IP67 module
  • Operating temperature: NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) — 4170: -30…60; 5015: -30…55 °C; Elementa 2 — -30…50 °C
  • Weight: NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) — 41 t; Elementa 2 — 42.5 t
  • Cycle life: NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) — 10,000 · Brochure (2023-11) for 314 Ah cell / NoahX-1500/4170: '10000 cycles @25℃, 0.5CP/0.5CP'. Press release (2023-09) claims cell cycle life 'exceeding 12,000 cycles' and product page for the 314 Ah cell lists 12000 cycles; Elementa 2 — 10,000 · Datasheet claim: 'up to 10,000 cycles with 0 degradation in first half year'; test conditions not published
  • Fire suppression: NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) — Water FSS / aerosol (optional); pack-level fire suppression, combustible gas emission and explosion venting (press release); Elementa 2 — automatic aerosol-based fire suppression system; water-based suppression optional; heat/smoke/gas sensors, active ventilation
  • Generation: NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) — NoahX 2.0, 2023; Elementa 2 — 2
  • Certifications: NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) — AS3000, GB36276, IEC61000, IEC62477, IEC62619, IEC62933, NFPA68/69, NFPA855, UL1973, UL9540A, UN3536, UN38.3; Elementa 2 — CE, IEC 61000-6-2/4, IEC 62477-1, IEC 62619, IEC 62933-5-2, IEC 63056, UL 1973, UL 9540, UL 9540A, UN38.3

Published by only one of the two: Max power per enclosure, Published durations, Round-trip efficiency, Calendar life, Announced.

Variants

Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) variants

VariantsEnergyPowerDuration
NoahX-1500/4170 — 4170 kWh, rated 0.5CP (2085 kW derived from published C-rate)4.17 MWh2.085 MW2 h
NoahX-1500/5015-L2 — 5015 kWh, standard 0.5P (2508 kW derived from published C-rate)5.015 MWh2.508 MW2 h

Trina Storage Elementa 2 variants

VariantsEnergyPowerDuration
5.015 MWh (314 Ah, 12 racks × 4 modules), 2–4 h5.015 MWhnot publishednot published
4.073 MWh (306 Ah, 1P416S10P, 10 racks × 4 packs), 2–6 h4.073 MWhnot publishednot published

Full model cards

Open Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) →Open Trina Storage Elementa 2 →

Other comparisons

Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2)Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs Trina Storage Elementa 2Pylontech Container L5000-BAT vs Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2)Pylontech Container L5000-BAT vs Trina Storage Elementa 2Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs CATL TENERSunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs Great Power Max-20HC-5000Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs HiTHIUM ∞Power 6.25MWhSunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs ZOE Energy Storage Z BOX-P 6200 2H