FieldAlphaESS Aster 5000CATL TENER
Max energy per enclosure5.016 MWh6.25 MWh
Max power per enclosure2.508 MW3.126 MW
Published durations2 h2 h
Segmentutility-scaleutility-scale
Statusshippingshipping
Cell chemistryLFPLFP
Cell capacitynot published587 Ah
Cell configurationnot published1P104S×4×8P (pack 1P104S, 4 packs per rack = 1P416S, 8 racks in parallel)
Cell suppliernot publishednot published
Form factor20 ft container20 ft container
Block typeDC blockDC block
PCS integratednono
DC voltage1331.2 (rated) V1331.2 rated; 1040–1500 range V
Coolingliquid-cooledliquid-cooled
Ingress protectionIP55not published
Operating temperature-40…50 (battery module) °C-30…55 °C
Dimensions (L × W × H)6058 × 2438 × 2896 mmnot published
Weight43 t45 t
Energy densitynot publishednot published
Round-trip efficiencynot publishednot published
Cycle lifenot published8,000 · Cell-level figure from CATL 2026 brochure: 587 Ah cell ≥8,000 cycles (25 °C, 0.5P/0.5P, 70% SOH). System-level cycle life not published; CATL claims zero capacity/power degradation in first five years.
Calendar lifenot publishednot published
Warrantynot publishednot published
Fire suppressionaerosol + sprinkler (redundant dual-extinguishing) + explosion relief panelnot published
GenerationV01 (2025-05)TENER (2024); Chinese market designation 天恒 C2-L625
Announcednot published2024-04
CertificationsIEC 61000, IEC 62477, IEC 62619, IEC 62933, NFPA 69, UL 1973, UL 9540AGB 44240-2024, GB/T 34131-2023, GB/T 36276-2023, GB/T 44026-2024
Public datasheetyesyes

Where they differ

Only fields both manufacturers publish and where the values are not identical. Not a judgement — the right choice depends on the project.

  • Max energy per enclosure: Aster 5000 — 5.016 MWh; TENER — 6.25 MWh
  • Max power per enclosure: Aster 5000 — 2.508 MW; TENER — 3.126 MW
  • DC voltage: Aster 5000 — 1331.2 (rated) V; TENER — 1331.2 rated; 1040–1500 range V
  • Operating temperature: Aster 5000 — -40…50 (battery module) °C; TENER — -30…55 °C
  • Weight: Aster 5000 — 43 t; TENER — 45 t
  • Generation: Aster 5000 — V01 (2025-05); TENER — TENER (2024); Chinese market designation 天恒 C2-L625
  • Certifications: Aster 5000 — IEC 61000, IEC 62477, IEC 62619, IEC 62933, NFPA 69, UL 1973, UL 9540A; TENER — GB 44240-2024, GB/T 34131-2023, GB/T 36276-2023, GB/T 44026-2024

Published by only one of the two: Cell capacity, Cell configuration, Ingress protection, Dimensions (L × W × H), Cycle life, Fire suppression, Announced.

Variants

AlphaESS Aster 5000 variants

VariantsEnergyPowerDuration
Aster 5000 (AlphaCS-H20-DC-LC-EX, 12 clusters, 0.5 P)5.016 MWh2.508 MW2 h

CATL TENER variants

VariantsEnergyPowerDuration
6.25 MWh 0.5P (2 × 1562.82 kW); brochure states 2 h/4 h system compatibility6.25 MWh3.126 MW2 h

Full model cards

Open AlphaESS Aster 5000 →Open CATL TENER →

Other comparisons

Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs CATL TENERGotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs AlphaESS Aster 5000Pylontech Container L5000-BAT vs CATL TENERPylontech Container L5000-BAT vs AlphaESS Aster 5000Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs CATL TENERSunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs AlphaESS Aster 5000CATL TENER vs Great Power Max-20HC-5000CATL TENER vs HiTHIUM ∞Power 6.25MWh