▮▮Coloprice

BESS comparison

CATL TENER vs HiTHIUM ∞Power 6.25MWh

Both columns come from what CATL and HiTHIUM publish. Fields either maker does not publish are marked «not published»; we do not estimate or rank.

Specifications side by side

FieldCATL TENERHiTHIUM ∞Power 6.25MWh
Max energy per enclosure6.25 MWh6.25 MWh
Max power per enclosure3.126 MW3.125 MW
Published durations2 h2 h · 4 h
Segmentutility-scaleutility-scale
Statusshippingshipping
Cell chemistryLFPLFP
Cell capacity587 Ah1175 Ah
Cell configuration1P104S×4×8P (pack 1P104S, 4 packs per rack = 1P416S, 8 racks in parallel)4*1P416S (4h) / 8*1P416S (2h)
Cell suppliernot publishednot published
Form factor20 ft container20 ft container
Block typeDC blockDC block
PCS integratednono
DC voltage1331.2 rated; 1040–1500 range V1040–1500 (nominal 1331.2) V
Coolingliquid-cooledliquid-cooled
Ingress protectionnot publishedIP55
Operating temperature-30…55 °C-30…55 °C
Dimensions (L × W × H)not published6058 × 2438 × 2896 mm
Weight45 t48 t
Energy densitynot published130 Wh/kg
Round-trip efficiencynot published95%
Cycle life8,000 · Cell-level figure from CATL 2026 brochure: 587 Ah cell ≥8,000 cycles (25 °C, 0.5P/0.5P, 70% SOH). System-level cycle life not published; CATL claims zero capacity/power degradation in first five years.not published
Calendar lifenot publishednot published
Warrantynot publishednot published
Fire suppressionnot publishedmulti-stage active fire detection and protection system (NFPA 855 compliant); type of agent not specified in datasheet
GenerationTENER (2024); Chinese market designation 天恒 C2-L625∞Pack+ platform (2024)
Announced2024-042024-12
CertificationsGB 44240-2024, GB/T 34131-2023, GB/T 36276-2023, GB/T 44026-2024IEC 61000, IEC 62477, IEC 62619, IEC 62620, IEC 62933, IEC 63056, NFPA 855, UL 1973, UL 9540, UL 9540A, UN 38.3
Public datasheetyesyes

Where they differ

Only fields both manufacturers publish and where the values are not identical. Not a judgement — the right choice depends on the project.

  • Max power per enclosure: TENER — 3.126 MW; ∞Power 6.25MWh — 3.125 MW
  • Published durations: TENER — 2 h; ∞Power 6.25MWh — 2 h · 4 h
  • Cell capacity: TENER — 587 Ah; ∞Power 6.25MWh — 1175 Ah
  • Cell configuration: TENER — 1P104S×4×8P (pack 1P104S, 4 packs per rack = 1P416S, 8 racks in parallel); ∞Power 6.25MWh — 4*1P416S (4h) / 8*1P416S (2h)
  • DC voltage: TENER — 1331.2 rated; 1040–1500 range V; ∞Power 6.25MWh — 1040–1500 (nominal 1331.2) V
  • Weight: TENER — 45 t; ∞Power 6.25MWh — 48 t
  • Generation: TENER — TENER (2024); Chinese market designation 天恒 C2-L625; ∞Power 6.25MWh — ∞Pack+ platform (2024)
  • Announced: TENER — 2024-04; ∞Power 6.25MWh — 2024-12
  • Certifications: TENER — GB 44240-2024, GB/T 34131-2023, GB/T 36276-2023, GB/T 44026-2024; ∞Power 6.25MWh — IEC 61000, IEC 62477, IEC 62619, IEC 62620, IEC 62933, IEC 63056, NFPA 855, UL 1973, UL 9540, UL 9540A, UN 38.3

Published by only one of the two: Ingress protection, Dimensions (L × W × H), Energy density, Round-trip efficiency, Cycle life, Fire suppression.

Variants

CATL TENER variants

VariantsEnergyPowerDuration
6.25 MWh 0.5P (2 × 1562.82 kW); brochure states 2 h/4 h system compatibility6.25 MWh3.126 MW2 h

HiTHIUM ∞Power 6.25MWh variants

VariantsEnergyPowerDuration
6.25 MWh 2h (587 Ah cells, 8*1P416S, 0.5P)6.25 MWh3.125 MW2 h
6.25 MWh 4h (1175 Ah cells, 4*1P416S, 0.25P)6.25 MWh1.562 MW4 h

Full model cards

Open CATL TENER →Open HiTHIUM ∞Power 6.25MWh →

Other comparisons

Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs CATL TENERGotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs HiTHIUM ∞Power 6.25MWhPylontech Container L5000-BAT vs CATL TENERPylontech Container L5000-BAT vs HiTHIUM ∞Power 6.25MWhSunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs CATL TENERSunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs HiTHIUM ∞Power 6.25MWhCATL TENER vs Great Power Max-20HC-5000CATL TENER vs ZOE Energy Storage Z BOX-P 6200 2H