HyperStrong HyperBlock M (AC version) vs LG Energy Solution JF2 AC LINK (2HR / 4HR)

Both columns come from what HyperStrong and LG Energy Solution publish. Fields either maker does not publish are marked «not published»; we do not estimate or rank.

Specifications side by side

FieldHyperStrong HyperBlock M (AC version)LG Energy Solution JF2 AC LINK (2HR / 4HR)
Max energy per enclosure12.8 MWh5.11 MWh
Max power per enclosure3.2 MW2.55 MW
Published durations4 h2 h · 4 h
Segmentutility-scaleutility-scale
Statusshippingshipping
Cell chemistryLFPLFP
Cell capacity601 Ahnot published
Cell configuration8P416S / 16P416S14 packs in series × 6 racks in parallel (2HR)
Cell suppliernot publishednot published
Form factormodular blockmodular block
Block typeAC block (PCS integrated)AC block (PCS integrated)
PCS integratedyesyes
DC voltage1123.2–1497.6 (rated 1331.2) Vnot published
Coolingliquid-cooledliquid-cooled
Ingress protectionContainer IP55, Pack IP65, PDU IP55IP55
Operating temperature-30…55 °C-30…50 °C
Dimensions (L × W × H)6058 × 2438 × 2896 mm7020 × 2570 × 2900 mm
Weight24 t48 t
Energy densitynot publishednot published
Round-trip efficiency93%not published
Cycle life10,000 · >10000cls@SOH70%, 0.5P, to achieve up to 20 years of operation life guaranteenot published
Calendar life20 ynot published
Warrantynot publishednot published
Fire suppressionCombustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protectiongas detection and active venting system, fire detection and alarm system
GenerationMagicBlock platform, 20252024
Announced2025-052024-11
CertificationsEN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120IEEE1547, IFC/CFC, NFPA 69, NFPA 72, NFPA 855, UL1642, UL1741 (SA, SB), UL1973, UL9540, UL9540A and large-scale fire testing, UN 38.3
Public datasheetyesyes

Where they differ

Only fields both manufacturers publish and where the values are not identical. Not a judgement — the right choice depends on the project.

  • Max energy per enclosure: HyperBlock M (AC version) — 12.8 MWh; JF2 AC LINK (2HR / 4HR) — 5.11 MWh
  • Max power per enclosure: HyperBlock M (AC version) — 3.2 MW; JF2 AC LINK (2HR / 4HR) — 2.55 MW
  • Published durations: HyperBlock M (AC version) — 4 h; JF2 AC LINK (2HR / 4HR) — 2 h · 4 h
  • Cell configuration: HyperBlock M (AC version) — 8P416S / 16P416S; JF2 AC LINK (2HR / 4HR) — 14 packs in series × 6 racks in parallel (2HR)
  • Ingress protection: HyperBlock M (AC version) — Container IP55, Pack IP65, PDU IP55; JF2 AC LINK (2HR / 4HR) — IP55
  • Operating temperature: HyperBlock M (AC version) — -30…55 °C; JF2 AC LINK (2HR / 4HR) — -30…50 °C
  • Dimensions (L × W × H): HyperBlock M (AC version) — 6058 × 2438 × 2896 mm; JF2 AC LINK (2HR / 4HR) — 7020 × 2570 × 2900 mm
  • Weight: HyperBlock M (AC version) — 24 t; JF2 AC LINK (2HR / 4HR) — 48 t
  • Fire suppression: HyperBlock M (AC version) — Combustible gas detection, temperature sensor, smoke detection, cabin level aerosols, deflagration venting panels, water fire protection; JF2 AC LINK (2HR / 4HR) — gas detection and active venting system, fire detection and alarm system
  • Generation: HyperBlock M (AC version) — MagicBlock platform, 2025; JF2 AC LINK (2HR / 4HR) — 2024
  • Announced: HyperBlock M (AC version) — 2025-05; JF2 AC LINK (2HR / 4HR) — 2024-11
  • Certifications: HyperBlock M (AC version) — EN50549, EN61000, G99, IEC60730, IEC62477, IEC62619, IEC62933, IEEE1547, NFPA855/68/69, UL1741, UL1973, UL9540, UL9540A, UN38.3, VDE4110, VDE4120; JF2 AC LINK (2HR / 4HR) — IEEE1547, IFC/CFC, NFPA 69, NFPA 72, NFPA 855, UL1642, UL1741 (SA, SB), UL1973, UL9540, UL9540A and large-scale fire testing, UN 38.3

Published by only one of the two: Cell capacity, DC voltage, Round-trip efficiency, Cycle life, Calendar life.

Variants

HyperStrong HyperBlock M (AC version) variants

VariantsEnergyPowerDuration
HSL3G71-06400 — 6.4 MWh / 400 kW×46.4 MWh1.6 MW4 h
HSL3G71-12800 — 12.8 MWh / 400 kW×812.8 MWh3.2 MW4 h

LG Energy Solution JF2 AC LINK (2HR / 4HR) variants

VariantsEnergyPowerDuration
JF2 2HR AC LINK — 5.11 MWh / 2.55 MW, 690 Vrms, 0.5 CP5.11 MWh2.55 MW2 h
JF2 4HR AC LINK — 5.11 MWh / 1.32 MW (6 × 220 kVA), 690 Vrms, 0.25 CP5.11 MWh1.32 MW4 h

Full model cards

Open HyperStrong HyperBlock M (AC version) →Open LG Energy Solution JF2 AC LINK (2HR / 4HR) →

Other comparisons

Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs LG Energy Solution JF2 AC LINK (2HR / 4HR)Gotion High-Tech Gotion Grid 5 MWh (ESD1331-05P5015) vs HyperStrong HyperBlock M (AC version)Pylontech Container L5000-BAT vs LG Energy Solution JF2 AC LINK (2HR / 4HR)Pylontech Container L5000-BAT vs HyperStrong HyperBlock M (AC version)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs LG Energy Solution JF2 AC LINK (2HR / 4HR)Sunwoda Energy NoahX 2.0 (NoahX-1500/4170, NoahX-1500/5015-L2) vs HyperStrong HyperBlock M (AC version)CATL TENER vs LG Energy Solution JF2 AC LINK (2HR / 4HR)CATL TENER vs HyperStrong HyperBlock M (AC version)